TEB122050

TEB122050 Circuit Breaker

Price Quote Get an up to date pricing and availability quote for this product. Order online or over the phone.

Part Number:
Quantity Requested:
Your Email:
Full Name:
Contact Phone:
Company:

Quality Commitment

Serving our customers with quality and safety first.

  •   AS9120 Certified
  •   Audited supply chain
  •   ITAR Registered
  •   DDTC Registered
  •   HAZMAT Certified
  •   Customer service objectives
  •   Every product 100% inspected
AS9120 Certified by SAI Global

Datasheet. TEB122050 specification

Body Style
The style designation indicating the configuration that most nearly corresponds to the appearance of the body.

rectangular dimensional envelope

Overall Length
The dimension measured along the longitudinal axis with terminated points at the extreme ends of the item.

6.312in. ⁓6-5/16"

Overall Height
The distance measured in a straight line from the bottom to the top of an item.

2.750in.

Overall Width
An overall measurement taken at right angles to the length of an item,in distinction from thickness.

3.380in.

Case Material
The element,compound,or mixture of which the case is fabricated,excluding any surface treatment.

plastic

Unthreaded Mounting Hole Diameter
The length of a straight line which passes through the center of an unthreaded mounting hole,and terminates at the circumference.

0.188in.

Pole Quantity
The number of poles included in the item.

2

Mounting Facility Type And Quantity
Indicates the type and number of facilities by which the item is mounted.

2 unthreaded hole

Maximum Continuous Load Current Rating Per Pole
The maximum current load that each pole is rated to carry continuously.

50.0 amperes ac all locations

Operating Voltage Type And Rating Per Pole In Volts
Indicates the type and value of operating voltage for which each pole is designed to operate,expressed in volts.

240.0 ac all locations

Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
Indicates the type and value of the maximum short circuit current that the item will successfully interrupt,per pole,at the specified rated voltage,expressed in amperes.

10000.0 ac all locations

Circuit Protection Type
Indicates the type of electrical condition that will cause the device to trip.

overcurrent all locations

Trip Release Method
The means by which the trip mechanism is released.

THERMAL-Magnetic all locations

Trip Release Characteristic
Denotes the type of trip release action.

time delay all locations

Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
The continuous current rating per pole at which the device must trip in a specified time,expressed in percent.

125.0 all locations

Reset Method
The means provided to reposition the mechanism so that the device is ready to function.

manual

Main Contact Tripping Mechanism Type
Indicates the type of mechanism provided for tripping main contacts.

trip free

Manual Actuator Type And Quantity
Indicates the type and number of actuators provided for manual control.

1 toggle

Actuator Function
Denotes the action imparted by actuator operation.

TRIP-Reset

Actuator Position Designation
An indication of the designated position of the actuator.

at pole one

Trip Delay Time In Seconds Per Rated Continuous Current
The length of time,expressed in seconds,that an overload may exist before the device will trip at a specified continuous current.

240.000 at 200 pct all locations

Trip Release Ambient Temp Rating
The temperature of the medium surrounding the trip release at which it can be operated continuously.

40.0 deg celsius all locations

Frequency In Hertz
The cycles per second /hertz/ of the alternating current.

60.0 all locations

Test Data Document
The specification,standard,drawing,or similar instrument that specifies environmental and performance requirements or test conditions under which an item is tested and establishes acceptable limits within which the item must conform identified by an alphabetic and/or numeric reference number. includes the commercial and government entity (cage) code of the entity controlling the instrument.

81348-W-C-375 specification (includes engineering type bulletins, brochures, etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type data on certain environmental and performance requirements and test conditions that are shown as "typical", "average", "", etc.) .

Terminal Type And Quantity
Indicates the type and number of terminals for providing electrical connection.

2 screw

Answers.

What is the overall width?

3.380 inches

What is the NSN for TEB122050?

5925-00-504-0996

How is this classified for shipping?

Schedule B number: 8536200040
Automatic circuit breakers, for a voltage not exceeding 1,000 v

What's the federal classification of TEB122050?

FSC 5925 ⁓ Circuit breakers

Excluding relays.

NSN 5925-00-504-0996 CIRCUIT BREAKER

3.380" overall width 6.312" overall length

NIIN
005040996
NIIN Date
07/13/74
Schedule B
8536200040 
Name Code
00136
FIIG
A030A0
QUP
 
Historical Price
$115.00 EA
DEMIL / ITAR
Uncontrolled item (Code A)
Hazmat
No hazard information available from HMIRS.
MSDS
N/A
Precious Metals
Metal content unknown
Enviromental
N/A
Electrostatic ESD & EMI
No ESD or EMI sensitivity

Major End Users Countries and entities

  • - Republic of Korea 
  • - Turkey 

Availability for TEB122050 A member of our team will provide you with a price and availability quote

Request a Quote »

Similar by Design Other circuit breakers with similar characteristics

Nothing similar to this part number was found in our inventory

TEB122050 / Circuit breakerWhat is the formal definition of this item?

A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. may include provisions for manual operation. at least one set of contacts must be in series with the actuating element(s). a combination of semiconductor and passive devices may be used in lieu of contacts. for automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). for items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. excludes circuit breaker box and magneto "breaker" assemblies. see also switch (as modified); and controller.