NSN 5925-00-628-7776 NIIN 006287776 — Circuit Breaker Tripper

NSN
Item Name
Assigned
DEMIL
Shelf Life
UOM
Using Services
NSN:
5925-00-628-7776
5925006287776
Description:
TRIPPER,CIRCUIT BREAKER
NSN Assigned:
01-JAN-63
DEMIL:
NO
Shelf Life:
N/A
UOM:
1 EA
Using Services:
Navy

Price Quote Get an up to date pricing and availability quote for this product. Order online or over the phone.

Part Number:
Quantity Requested:
Your Email:
Full Name:
Contact Phone:
Company:

Quality Commitment

Serving our customers with quality and safety first.

  •   AS9120 Certified
  •   Audited supply chain
  •   ITAR Registered
  •   DDTC Registered
  •   HAZMAT Certified
  •   Customer service objectives
  •   Every product 100% inspected
AS9120 Certified by SAI Global

5925-00-628-7776 Specification Set by the OEM (see RNCC code 3)

Body Style AAQL:

rectangular dimensional envelope

Overall Length ABHP:

8.438in. ⁓8-29/64"

Overall Height ABKW:

3.875in.

Overall Width ABMK:

4.500in.

Unthreaded Mounting Hole Diameter AEBV:

0.406in. and 0.531in.

Pole Quantity AKPX:

3

Mounting Facility Type And Quantity AXHR:

6 unthreaded hole

Features Provided CBBL:

adjustable trip release

Maximum Continuous Load Current Rating Per Pole CPLM:

300.0 amperes ac all locations and 300.0 amperes dc all locations

Operating Voltage Type And Rating Per Pole In Volts CPRF:

500.0 ac all locations and 250.0 dc all locations

Circuit Protection Type CPRH:

overcurrent all locations

Trip Release Method CPRJ:

THERMAL-Magnetic all locations

Trip Release Characteristic CPRL:

instantaneous all locations and time delay all locations

Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent CPRN:

105.0 all locations

Adjustable Trip Setting Current Range Per Pole In Amps CPSF:

+1380.0/+2280.0 ac all locations and +1600.0/+2285.0 dc all locations

Trip Delay Time In Seconds Per Rated Continuous Current CQWN:

25.000 at 600 pct all locations

Trip Release Ambient Temp Rating CRCF:

50.0 deg celsius all locations

Frequency In Hertz FREQ:

60.0 all locations

Terminal Type And Quantity TTQY:

6 screw

Cross Reference Parts Part numbers that meet the specification outlined on this page and set by the OEM

Part Number
Cage
RNCC
RNVC
DAC
RNAAC
Status
MSDS
SADC
Part Number:
ETN6732
Cage Code:
30086
RNCC:
3
RNVC:
2
DAC:
X
RNAAC:
XX
Status:
A
MSDS:
SADC:
Part Number:
575-4110-1854038REVDPC29TRIP
Cage Code:
80064
RNCC:
5
RNVC:
2
DAC:
X
RNAAC:
XX
Status:
A
MSDS:
SADC:
Part Number:
3778-808REVDPC29TRIP
Cage Code:
96169
RNCC:
5
RNVC:
2
DAC:
X
RNAAC:
XX
Status:
A
MSDS:
SADC:

Identification Item Identification Guide (IIG) and Item Name Code (INC)

INC
FIIG
Concept No.
App. Key
Cond. Code
Status
INC:
04558
FIIG:
A030A0
Concept No.:
App. Key:
B
Cond. Code:
1
Status:
A
BODY STYLE RECTANGULAR DIMENSIONAL ENVELOPE style nsn 5925-00-628-7776

Definition Definition of approved item name (AIN): "TRIPPER,CIRCUIT BREAKER"

An electromechanical device which releases the holding mechanism and permits the contacts of a circuit breaker to open. It is a replacement part of a circuit breaker. Does not include relays. See also thermal release, circuit breaker.

Packaging & Dimensions Packaging instructions, special markings, and approx. weight/dims

Pack Size
Pack Weight
Item Weight
Item Dim.
Pack Size:
--
Paclk Weight:
5.5000lbs
Item Weight:
--
Item Dim:
--
Container
OPI
SPI No.
SPI Rev.
SPC Mkg.
LVL A
LVL B
LVL C
Container:
--
OPI:
O
SPI No.:
SPI Rev.:
SPC Mkg:
00
LVL_A:
Q
LVL_B:
Q
LVL_C:
LVL A Code (LVL_A) Q

Packing shall be accomplished in accordance with table c.ii for the packing level specified. closure, sealing and reinforcement shall be in accordance with applicable specification for shipping container.

LVL B Code (LVL_B) Q

Packing shall be accomplished in accordance with table c.ii for the packing level specified. closure, sealing and reinforcement shall be in accordance with the appropriate shipping container specification.

Procedure Indicator Code (OPI) O

Options can be exercised as to specific method of preservation or dod approved packaging materials to be used. however, basic preservation method shall be retained, supplemental data shall be complied with, and unit package dimensions shall not be increased by more than one inch. equal or better protection shall be given the item and there shall be no increase in the package cost.

Special Markings Code (SPC_MKG) 00

No special marking.

  Packaging Codes

OPI: Optional Procedure Indicator Code. A one position alpha code that indicates the allowable deviations from the prescribed requirements.

SPI No.: Special packaging instructions number.

LVL A/B/C: Indicates the type of shipping container required for level A, B, or C maximum packing protection.

SPC Mkg: A two position code that identifies the special markings applied to the container, which is part of the total pack to protect the contained item during preservation, packing, storage, transit and removal from the pack.

5925-00-628-7776 Material Hazmat, Precious Metals, Criticality, Enviroment, and ESD

HMIC
PMIC
ESD
ENAC
ADPE
CRITL
HMIC:
P
PMIC:
U
ESD:
ESD:
ADPE:
CRITL:
X
Hazmat (HMIC) P

Indicates there is no information in the hmirs. The nsn is in a fsc in table ii of fed std 313 and a msds may be required by the user. The requirement for a msds is dependent on a hazard determination of the supplier or the intended end use of item.

Precious Metals (PMIC) U

Precious metal content is unknown

Criticality X

The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.

  Identification Codes

HMIC: Hazardous Material Indicator Code. A one position code that identifies a hazardous item.

PMIC: Precious Metal Indicator Code. A one position code which identifies items that have precious metals as part of their content. precious metals are those metals generally considered to be uncommon, highly valuable, and relatively superior in certain properties such as resistance to corrosion and electrical conductivity.

ESD: Electrostatic Discharge. Indicates if an item is susceptible to electrostatic discharge or electromagnetic interference damage. electrostatic discharge damage occurs when an accumulation of static electricity generated by the relative motion or separation of materials is released to another item by direct contact. electromagnetic interference damage occurs when an item comes into proximity with an electrostatic or magnetic field.

ENAC: Enviromental Attribute Code. Identifies items with environmentally preferred characteristics.

CRITL: Criticality Indicator Code. Indicates an item is technically critical by tolerance, fit, application, nuclear hardness properties, or other characteristics.